Fiona Stanley Hospital, ECU team up to reduce ICU noise


Friday, 03 May, 2024

Fiona Stanley Hospital, ECU team up to reduce ICU noise

Fiona Stanley Hospital is working with Edith Cowan University on improving acoustic design with an aim to decrease noise levels in intensive care units (ICUs).

Research suggests that around half of ICU patients experience sleep disturbance due to noise which can hinder recovery and negatively impact their health.

As a part of the project, ECU Adjunct Senior Research Fellow Dr Emil Jonescu and Director of ICU Research at Fiona Stanley Hospital Professor Ed Litton, conducted a research study at a 40-bed ICU in Fiona Stanley Hospital, Perth. The study involved clinicians, medical practitioners, academics and industry specialist consultants.

It investigated the impact of noise on patient sleep quality and clinician performance and provides practical recommendations for design approaches to noise mitigation.

The room acoustics analysis revealed that at times maximum noise levels in the ICU ranged from 60 to 90 dB(A), surpassing the thresholds for sleep disruption outlined by the World Health Organisation guidelines.

Beeps and alarms

Noise was primarily caused by alarms from medical equipment and discussions among clinical staff, and was a common problem across all ICUs, Jonescu said.

“In the ICU there are a lot of beeps and alarms from machines and some of that noise can’t be mitigated because of the important information provided for clinicians,” he said.

“Our aim was to try and find the optimal balance of good information flow for clinicians and rest and recovery for patients, and we found there are certainly some design improvements that can be made.”

Professor Litton said that sleep disruption was a major issue raised by patients in intensive care and that problems with sleep could often persist after discharge, causing distress and creating a barrier to recovery.

“Thinking holistically about how we make the experience as comfortable as possible for patients whilst in intensive care is so important,” he said.

“This means we need to collaborate broadly, including with design experts, to address the issues that matter for our patients.”

Staff perceptions

Part of the study investigated health professionals’ perceptions of noise impact on patient sleep and staff duties in the ICU.

Staff reported ICU noise negatively impacted their work performance, patient connection and job satisfaction.

“They indicated that their biggest concern was the impact to patient sleep quality; however, they also believe a quieter ICU would improve clinicians’ thinking ability,” Jonescu said.

“ICU Clinicians and patients share the same environment and it’s clear that improvements in noise levels will benefit everyone.”

Noise between rooms

Through a 3D modelling process, researchers simulated various acoustic treatment upgrades.

They found that room layout and equipment precluded many noise reduction options. These were limited to perimeter surface sound absorption, whereas direct transmission pathways and volume settings offered potential for more significant noise reductions.

“One of the most significant findings of the study was that by concentrating on noise reduction strategies for the partition walls between patient rooms, transference of noise from room to room can be significantly reduced,” Jonescu said.

“The findings showed a significant reduction of 14 decibels with the doors between rooms in the open position.”

Further research

Jonescu said the study identified potential for medical equipment designers to consider alarm speakers’ directivity focusing the sound towards sound-absorbing wall finishes and reducing noise exposure towards patients.

“Future research could also explore the minimum volume level that machines can operate at where there is no impact to clinicians’ ability to do their work,” he said.

“A reduction in volume from the default 100% maximum could have massive impact in reducing overall noise, and it wouldn’t cost anything.”

The study, Mitigating Intensive Care Unit Noise: Design-Led Modelling Solutions, Calculated Acoustic Outcomes, and Cost Implications, was published in HERD: Health Environments Research & Digital Design Journal.

Image credit: iStock.com/sudok1

Related News

New public health campaign to improve pregnancy outcomes

The Preterm Birth Prevention campaign 'See, Stop, Scan' aims to promote engagement...

Feedback sought on genomic-led cancer control

The framework is designed to guide health professionals, researchers, health services and policy...

Can you die from long COVID? The answer is not so simple

Nearly five years into the pandemic, COVID is feeling less central to our daily lives.


  • All content Copyright © 2024 Westwick-Farrow Pty Ltd